ProcessLogix R500.1 SP1 and R510.0 Station Update 4 9
37264 New InvokePopup method should allow the optional parameters You must specify ALL parameters, e.g.,
window.external.InvokePopup
"c:\honeywell\client\abstract\MyPopup.htm",0,0,0
37273 Inconsistency displaying parameter of invalid point between DSP and
HMIWeb alphanumeric use scripting to hide elements bound to
invalid points
37826 Pt Detail Trend "Value At" data displayed in "E" format when > 99.5
38111 When the field within the group is clicked, the field does not go black,
ready for data entry, the numerics have to be deleted to enter data.
Ungroup the objects.
38148 Scripts in onshapeload and onshapeunload events can't reference
shape objects directly Script should use me.Objects("SPInd").value
instead of SPInd.value
38520 Need to be able to set plot info for bound plots.
38522 Need to be able to set plot position at runtime
39090 Signon Manager (SOM) does not accurately pass DOMAIN identity to
Station
39253 ActiveX documents on HMIWeb pages do not print
39280 Page parameters can't be used with the SetCustomProperty method
on dynamic shapes.
Use the following script:
shape001.setcustomproperty "ParameterType",
"ParameterName", "{%CurrentPoint%}".
40038 One sentence is not able to be translated in connection properties
40352 Station shows the CurrentPageLocation as //machine/...., when it
should be \machine\....
42015
Display problem after minimizing station: GTAC AS01 SR#1-30104532 (PAR
1-30104532)
43528 Printer preferences override the page setup settings in station Configure your printer to use landscape orientation by
default.
45611 InProcess Safebrowse does not let contained active documents
handle the ENTER key
45859 If you start station with the -sf flag for full screen operation the help
is always at the back.
47168 Station allows displays to be called up from a web share but does not
recognize the web share when it is on the display path.
47258 Shutting down IE with a HMIWeb page displayed causes IE to crash
47407 When you have 2 of the same string in a combobox, only the first one
is selectable.
48884 Display element's location changes in print preview.
49097 Station start problem if default.stn is absent
49655 Navigation problems in station when entering entire path of file in
command zone.
Create a display page with a hyperlink.The path of
the hyperlink is the same as that of the document
created. Save the display page in a directory that is
part of the Display Paths. Call the display page &
click on the hyperlink.
Table 3 Known Problems in Station
ISR Description Workaround